UPS Sizing Versus Battery Runtime
UPS sizing and runtime answer different questions. This fixture needs 1080 W and 1200 VA. Usable energy is 3840 Wh, battery-side power is 1000 W, and runtime is 3.84 hours.
Formula, variables and conditions
P = sum(watts × quantity) S = sum(watts × quantity / pf) Required watts and volt-amperes apply the margin once. E = V × Ah × (socStart − socEnd) × soh Pbattery = P / efficiency + idle runtime = E / Pbattery
Variables and units
- Margin: fraction from 0 to 1, applied once to both watts and volt-amperes.
- V and Ah: nominal battery voltage and ampere-hours.
- socStart, socEnd, soh: fractions. Ending state of charge cannot exceed the start. State of health is greater than 0 and at most 1.
- efficiency: greater than 0 and at most 1. Idle power is in watts and may be 0.
Conditions
- CASE-004 and the UPS runtime teaching case use this same TC-018 input. There is no second measured scenario.
- Efficiency is not multiplied into E. The battery-runtime calculator does the opposite: it multiplies efficiency into energy and divides by the AC load.
- SRC-010 is the project model. Its calculation-record URL is null. It is not a manufacturer runtime curve.
Worked example
One load, quantity 1, idle 0 W. Constant voltage and constant load.
- Load
- 900 W at power factor 0.9
- Margin
- 0.2
- Required capacity
- 1080 W and 1200 VA
- Battery window
- 48 V, 100 Ah, state of charge 1 to 0.2, state of health 1
- Efficiency
- 0.9
- Energy / battery power / runtime
- 3840 Wh / 1000 W / 3.84 hours
E = 48 × 100 × 0.8 = 3840 Wh. Battery power = 900 / 0.9 = 1000 W. Runtime = 3840 / 1000 = 3.84 hours. Apparent power before margin is 900 / 0.9 = 1000 VA, then 1000 × 1.2 = 1200 VA.
Boundaries and common mistakes
Boundaries
- No Peukert effect, chemistry, temperature, BMS limit or voltage cutoff.
- Redundancy, transfer and protection coordination are not evaluated.
- If you put these battery numbers into the battery-runtime calculator, efficiency multiplies the 3840 Wh and the load stays 900 W. That is a different estimate and is not this 3.84 hour result.
Common mistakes
- Sizing only watts and forgetting volt-amperes when the power factor is below 1.
- Applying the margin twice.
- Putting UPS efficiency into the energy term and also dividing the load by efficiency.