Battery Runtime from Watt-Hours

Deliverable energy is voltage × ampere-hours × state-of-charge window × health × discharge efficiency. The locked fixture delivers 864 Wh and runs 8.64 hours at 100 W.

Formula, variables and conditions

E = V × Ah × (socStart − socEnd) × soh × efficiency
runtime hours = E / loadW

Variables and units

  • V: nominal volts, greater than 0.
  • Ah: capacity, greater than 0.
  • socStart and socEnd: 0 to 1, and the end must not exceed the start.
  • soh and efficiency: greater than 0 and at most 1.
  • loadW: constant watts, greater than 0.

Conditions

  • Voltage and load stay constant for the whole interval.
  • This is not the UPS runtime model. UPS energy omits efficiency, then divides the AC watts by efficiency to get battery-side power.
  • SRC-010 URL on the calculation record is null. No manufacturer discharge curve is implied.

Worked example

Locked TOOL-016 fixture.

Battery
12 V, 100 Ah
State of charge
1 to 0.2
Health / efficiency
1 / 0.9
Load
100 W
Deliverable energy
864 Wh
Runtime
8.64 hours

E = 12 × 100 × 0.8 × 1 × 0.9 = 864 Wh. Runtime = 864 / 100 = 8.64 hours.

Boundaries and common mistakes

Boundaries

  • Peukert effect, temperature, chemistry, BMS limits and voltage cutoff are not modeled.
  • The result is not an installation approval.
  • A 48 V UPS teaching fixture belongs to the UPS guide. Do not relabel 8.64 hours as that 3.84 hour result.

Common mistakes

  • Omitting efficiency here, or applying it a second time to the load.
  • Using a state-of-charge end above the start. The model rejects that order.
  • Converting ampere-hours to hours by dividing by current when the known load is watts and the efficiency term is required.