Lagging Load Power Factor Correction

The required capacitive vars are P times the drop in tan(acos pf). For 10000 W from 0.8 to 1.0, that is 7500 var. Leading loads are rejected.

Formula, variables and conditions

tan(pf) = sqrt(1 − pf²) / pf
Qc = 0 when the power factors are equal; otherwise Qc = P × (tan(pf_before) − tan(pf_target))
Delta branch: C = Qc / (6 × π × f × Vll²)
Star branch: C = Qc / (2 × π × f × Vll²)
Single-phase: C = Qc / (2 × π × f × V²)

Variables and units

  • P: active power in W, greater than 0.
  • pf_before and pf_target: greater than 0 and at most 1. The target must not be below the initial value.
  • V: system voltage in V. For delta and star it is line-to-line.
  • f: frequency in Hz.
  • C: capacitance per branch in farads. Multiply by 1e6 for microfarads.

Conditions

  • Load direction must be lagging. A leading load returns LEADING_LOAD and no capacitance.
  • Resonance, harmonics, switching steps, protection and code compliance are marked not-evaluated.
  • SRC-004 stores the Schneider compensation URL. accessedAt on that record is null.

Worked example

Locked TC-006 input: delta connection, 50 Hz, lagging.

Active power
10000 W
Power factor
0.8 to 1.0
Voltage / frequency
400 V line-to-line / 50 Hz
Connection
delta
Required vars
7500 var
Capacitance per delta branch
49.735919716217 µF

tan(acos(0.8)) = 0.75 and tan(acos(1)) = 0, so Qc = 10000 × 0.75 = 7500 var. The unit test locks the delta branch farads times 1e6 at 49.735919716217. The same inputs in star use divisor 2 instead of 6, so that branch capacitance is three times the delta value.

Boundaries and common mistakes

Boundaries

  • An unchanged target of 0.8 returns exactly 0 var and 0 F.
  • A target below 0.8 is rejected.
  • This is not a capacitor-bank specification. Discharge, switching and harmonic duty are outside the model.

Common mistakes

  • Correcting a leading load with the lagging formula. The calculator rejects that direction.
  • Using the single-phase divisor on a line-to-line delta voltage.
  • Treating 7500 var as a kilovar equipment rating without checking voltage and steps.