Power Factor Correction Calculator

Estimate the ideal capacitive compensation needed to move a lagging load toward a target power factor.

01 / Inputs

Load and system

02 / Result

Power factor correction

Waiting for input

Enter load and system values to estimate the required capacitive compensation.

Method and boundaries

Qc = P [tan(acos pf₁) − tan(acos pf₂)]. Single: C = Qc/(2πfV²); delta: C = Qc/(6πfVLL²); star: C = Qc/(2πfVLL²).

Estimate for a lagging inductive load only. Resonance, harmonics, switching stages, protection, equipment suitability, and code compliance are not evaluated.

Method and boundaries

Qc = P[tan(acos pf₁) − tan(acos pf₂)]. Per-branch capacitance depends on single-phase, delta, or star connection; three-phase input voltage is line-to-line voltage.

Resonance, harmonics, switching stages, protection, equipment suitability, and code compliance are not evaluated. SRC-004 · model 1.0.0 · user-input-v1.