TOPIC-03 · Engineering guide
DC Voltage Drop on a Two-Wire Cable
DC drop on a two-wire run is 2 × I × L × r. At 20 A, 50 m and 0.003 Ω/m the drop is 6 V, the end voltage is 224 V, and 100 × 6 / 230 is 2.609% when rounded to three decimals.
Formula, variables and conditions
DC: ΔV = 2 × I × L × r Single-phase AC: ΔV = 2 × I × L × (r × pf ± x × sinφ) Balanced three-phase: ΔV = sqrt(3) × I × L × (r × pf ± x × sinφ) The reactance sign follows the declared lagging or leading direction. L is one-way length in metres and r is ohms per metre after the temperature correction you enter.
Variables and units
- I: current in A.
- L: one-way route length in m. The DC and single-phase formulas already include the return path by the factor 2.
- r: conductor resistance in Ω/m at the stated temperature, divided by the parallel count.
- x: reactance in Ω/m. It is zero for DC and when reactance is explicitly ignored.
- Allowed drop percent: a user threshold, not an approval.
Conditions
- The English worked example sets temperature so the entered resistance is used as given, with one parallel path.
- Loss is 2 × I² × L × r for DC and single-phase, and 3 × I² × L × r for balanced three-phase. This example quotes drop, not the cost case.
- Chinese cable cases recompute GB/T 3956 resistances at 220 V. They are a different fixture, not a translation of these 230 V numbers.
Worked example
English teaching fixture CASE-001. Resistances are illustrative inputs, not a copied cable table.
- Circuit
- 230 V DC, 20 A
- One-way length
- 50 m
- Candidate A
- 0.003 Ω/m
- Candidate A drop
- 6 V, 2.609% of 230 V, end 224 V
- Candidate B
- 0.002 Ω/m
- Candidate B drop
- 4 V, 1.739% of 230 V, end 226 V
Both candidates are under the user-entered 3% threshold in this fixture. That comparison does not rate the conductor.
Boundaries and common mistakes
Boundaries
- No manufacturer table is reproduced.
- Ampacity, grouping, ambient correction, protection and installation rules are not evaluated unless you turn on the separate user-entered ampacity screen, which only compares numbers you type.
- The AC formulas are the model’s equations. This numeric example does not invent an AC fixture.
Common mistakes
- Using one-way resistance without the return path on a DC or single-phase circuit.
- Applying the √3 formula to a DC loop.
- Copying the English 230 V, 0.003 Ω/m example into a Chinese GB/T 3956 case. Those cases use 1.83 Ω/km and 1.15 Ω/km at 220 V.