What active, apparent and reactive power does the balanced three-phase model return at 400 V, 10 A and 0.8 lagging?

Teaching example—not a real installation.

01

Teaching inputs

Fixed values from the versioned calculation fixture.

Phase
balanced-three
Mode
from-current
Line voltage
400 V
Line current
10 A
Power factor
0.8 lagging

02

Calculation path

Each transformation stays visible.

  1. 1

    Find apparent power

    Balanced three-phase uses the square root of three on line voltage and line current.

    S = sqrt(3) × 400 × 10 = 6928.203230276 VA
  2. 2

    Apply the power factor

    Active power is apparent power times the displacement power factor.

    P = S × 0.8 = 5542.56258422 W
  3. 3

    Find lagging reactive power

    sin(acos(0.8)) is 0.6, and lagging keeps the positive sign.

    Q = S × 0.6 = 4156.921938165 var

03 · Result

The modeled outcome.

Teaching example—not a real installation. Results apply only to the stated fixture inputs.

MeasureCalculated valueInterpretation
Active power5542.56258422 WTC-004 lock
Apparent power6928.203230276 VAsqrt(3) × 400 × 10
Reactive power4156.921938165 varLagging

Teaching Example: power factor here is P/S for this sinusoidal operating point. It is not a motor efficiency.

04

Boundaries & sources

What the result does—and does not—support.

  • Harmonics, unbalance and code compliance are not evaluated.
  • The calculation record stores SRC-002 with url: null. The OpenStax pages are the register references, not a URL written onto that record.
  • This fixture stays at 400 V. It is not a converted 380 V example.