Transformer Turns Ratio

What secondary winding voltage and turns ratio does the ideal model return for 100 to 10 turns at 230 V?

Teaching example—not a real installation.

01

Teaching inputs

Fixed values from the versioned calculation fixture.

Phase and connection
Single-phase, single / single
Voltage mode
Winding-phase on both sides
Turns
N1 = 100, N2 = 10
Primary voltage
230 V
Solve mode
solve-voltage-ratio, then the reverse solve-turns-ratio check

02

Calculation path

Each transformation stays visible.

  1. 1

    Apply the ideal ratio

    Winding-phase voltages stay in proportion to the turns. Nothing in this step is a loaded voltage.

    V2 = V1 × N2 / N1 = 230 × 10 / 100
  2. 2

    Read the turns ratio

    The ratio reported with the voltage solution is N1/N2.

    N1 / N2 = 100 / 10 = 10
  3. 3

    Reverse the known voltages

    The unit test also solves the turns ratio from 230 V and 23 V and gets 10. That is the same fixture run backwards, not a second installation.

    V1 / V2 = 230 / 23 = 10

03 · Result

The modeled outcome.

Teaching example—not a real installation. Results apply only to the stated fixture inputs.

MeasureCalculated valueInterpretation
Secondary voltage23 VIdeal magnitude
Turns ratio10100 / 10
Reverse ratio10From 230 V and 23 V

Teaching Example: the ideal model returns 23 V and a turns ratio of 10. It does not estimate regulation.

04

Boundaries & sources

What the result does—and does not—support.

  • No impedance drop, regulation, vector-group shift, taps or unbalance.
  • A wye line-to-line voltage would be divided by sqrt(3) first. This fixture does not do that.
  • The result does not select a transformer.

Method references

PowerEngineerLab internal method · TOOL-021 model 1.1.0 · dataset user-input-v1

SRC-058 OpenStax, induced EMF and magnetic flux (checked 2026-10-14)