Transformer Voltage Regulation Calculator

Estimate voltage regulation for a declared single-phase or balanced three-phase per-unit series model.

#62 · CANDIDATE-062

Transformer voltage regulation

Phase model

R/X are percent values on the same per-unit base and reference side. At least one must be greater than zero.

02 / Results

Results

Enter the per-unit series parameters and load point, then calculate.

Calculation method

Ipu = λ(PF − j·s·sinθ); Epu = 1 + Ipu(Rpu + jXpu); regulation = (|Epu| − 1) × 100%.

Worked example

At full load, PF 0.8 lagging, R = 2% and X = 4%: Epu = 1.04 + j0.02, so regulation is approximately +4.01923%.

Frequently asked questions

Does this calculate the loaded terminal voltage?

No. It reports the voltage regulation percentage for the declared per-unit series model; it does not solve a source-voltage operating point.

Can I enter impedance values referred to different sides?

No. Rpu and Xpu must share one consistent base and reference side.

Does a negative result mean a fault?

No. Leading-load conditions can produce negative regulation in this model. It is not a fault or compliance assessment.